PS60 Permanent Supply Kiosk

The PS60 provides robust, weather-proof housing for a permanent electricity supply meeting the specifications of the DNOs for a permanent supply to a building or buildings. It is much faster to install than a brick construction and much more resistant to damage than a plastic enclosure.

Delivery Information:

This enclosure and its plinth are delivered on a pallet and will require a forklift to offload from the carrier.

Key Features

  • Designed to house meters, distribution boards and other electrical equipment rated up to approximately 100 A, or 60 to 70 kVA, depending on the DNO.
  • Not intended to house a CT chamber.
  • Separate segregated lockable compartments for BNO and DNO.
  • Louvres at top and bottom sides of cabinet for ventilation. Can be manufactured without louvres if a higher IP rating is required.
  • IP24 rating for models with ventilation louvres.
  • IP46 rating for models without ventilation louvres.
  • IK10 Impact rating.
  • Fully sealed door aperture.
  • Two tri-key camlocks top and bottom, and one central staple with padlock shroud on each door.
  • 30° peaked roof on a 2° slope down away from the door.
  • Available in three grades of stainless steel.
  • Smooth polyester powder coated finish.
  • 12mm Plywood Backboard included in each compartment.
  • Earthing studs fitted to both body and door.
  • Optional plinth to be installed into the ground before attaching the cabinet for increased stability.
  • Optional accessories for the protection of electrical and electronic equipment.
  • Detachable lifting brackets.
Design Approved by SP/ENW as alternative to brick housing.

Product Dimensions

EnclosureProduct Dimensions
(h x w x d, mm)
Backboard**
(h x w, mm)
Compartment Size**
(h x w x d, mm)
Weight
(kg)
PS601265* x 1250 x 430650 x 4501125 x 622 x 41485

* Height excluding plinth of 300 mm; **Each unit contains two compartments and now contains two backboards.

Check Product Dimensions of all Ritherdon Cabinets and Feeder Pillars.

Product Documentation

Accessory Options

  • Optional Plinth (Recommended)
  • Consumer Unit
  • Heater & Fan Kits
  • LED Light
  • Electrical Sockets
  • Shelf Kit
  • 19″ Rack Fixed

Modification Options

  • Access Panels
  • Cable Entry Holes
  • Removal of Louvre Vents (subject to metalwork modification)
  • Alternative Locking Systems (subject to metalwork modification)

Lock Options

The PS60 Cabinets are supplied with two tri key camlocks top and bottom and one central staple with padlock shroud as standard (on each door).  Alternative lock options are as follows:

Material Options

  • 4003 Grade Stainless Steel: Suitable for inland locations
  • 304 Grade Stainless Steel: Suitable for inland & coastal (<1 mile from coastline)
  • 316 Grade Stainless Steel: Suitable for coastline locations

Colour Options

  • RAL 9005 Black Gloss
  • BS4800 14C40 Dark Green Gloss
  • BS381C 631 Light Grey Gloss
  • BS381C 632 Dark Grey Gloss
  • Natural Finish* (304 & 316 Grades only)

Other colours available on request.

Delivery if in Stock is 48hrs from receipt of order* for finished and painted stock, or within 5 working days, for finished stock that requires powder coating. For Natural Finish from stock, lead time is 4 working days.

For large quantity orders, non-stock items and FireSeals Made-to-Measure, the lead time is 4 working weeks.  

Any prewired feeder pillars and cabinets with electrical items have a lead time of 4 to 8 working weeks.

Current Design time for any new sizes of FireSeals or other products, please add 2 working weeks to stated lead times.

*Any proforma orders received need to be paid before the order is processed and lead times start.

We always work to despatch orders sooner if we can. 

TOP

Make an enquiry

Name
Please state product name.
Enter delivery address and/or post code.

Contact Info

Make an enquiry

What rating are the chargers you are looking for the feeder pillar to power?
Please specify another rating.
Please specify number of chargers.
Would you prefer a Stainless Steel or a PVC feeder pillar?
If GRP is required, the PVC Feeder Pillar is electrically insulated and a suitable alternative for GRP.

Incoming DNO Specification

Please specify Supply Current in Amps.
Please specify cable area in mm2.
Please specify cable core: triple, copper, hybrid, etc.
What earthing choice would you prefer?
Which type of fault protection equipment do you require?
Do you require empty space for DNO equipment inside the feeder pillar?

Outgoing Specification

Which type of fault protection equipment do you require?
Do you require any of the following additional equipment inside the feeder pillar? Check all that apply.
Check any options that apply.
Please add any other electrical component options.
Do you require a power supply to anything outside the feeder pillar (not including the chargers) e.g. Lighting, CCTV ?

Contact Details

Please provide contact details so we can get in touch with a quote for your EV requirements.
Name
=
Following this submission, we will send you an opt-in email to confirm your consent. You can also unsubscribe at any time.

Contact Info